Dimensionamento compressore frigorifero
Stima potenza del motore, COP e portata volumetrica del compressore dalla potenza frigorifera e dalle temperature operative. I risultati sono stime preliminari, non selezioni definitive delle apparecchiature.

Standard engineering assumptions
Estimates Only: This calculator is provided for general informational purposes only. Results are approximate and may contain errors, omissions, or outdated information. They do not constitute legal, financial, engineering, tax, technical, or professional advice. Users are solely responsible for independently verifying all calculations, specifications, prices, regulations, and requirements with qualified professionals before making any decisions. By using this calculator, you acknowledge that the website owners, operators, and affiliates accept no responsibility or liability for any loss, damage, or decisions resulting from its use.
Il dimensionamento del compressore parte dalla potenza dell'evaporatore in kW e dal COP operativo: shaft power ≈ cooling duty ÷ COP. Il COP tipico è 3.5–5.0 per temperatura positiva (evaporazione a −5 °C) e 1.4–2.2 per surgelati (−35 °C). L'ammoniaca (NH₃) offre generalmente la migliore efficienza nei grandi impianti; CO₂ (R-744) è adatto a sistemi a carica ridotta e a cascata.
Motor power (kW) = cooling duty (kW) ÷ COP ÷ motor efficiency · Displacement (m³/h) = mass flow × suction specific volume
Verificato dagli ingegneri frigoristi ColdMatch
- 1Inserisci la potenza frigorifera richiesta in kW ricavata dal calcolo del carico.
- 2Scegli il refrigerante (NH₃, CO₂, R-448A/449A, propano) e la temperatura di evaporazione.
- 3Imposta la temperatura di condensazione per il tuo clima.
- 4Confronta potenza all'albero, COP e portata volumetrica, quindi richiedi gruppi compressori adatti.
What this calculator estimates — and what can change it
- Calculated heat load (kW)
- Target room temperature
- Ambient / external temperature
- Refrigeration technology (NH₃, CO₂, HFC/HFO)
- Redundancy / standby capacity
Dimensionamento compressore
- Refrigeration technology (NH₃, CO₂, HFC/HFO)
- Ambient / external temperature
- Redundancy / standby capacity
- Pull-down time
Limitations
This is a preliminary planning estimate based on the assumptions you entered, not a refrigeration-engineering design, a certified load calculation or a quotation. Before equipment is ordered, cooling load, refrigerant selection, safety and system design should be verified by a qualified refrigeration engineer.
Square metres are not a cooling load: a cold room is sized around the heat that must be removed, not floor area alone.
Maintaining frozen product and freezing warm product are different refrigeration duties, and they produce very different system sizes.
Two refrigeration quotations are not comparable until their design assumptions are comparable — and a low equipment price can hide a high lifetime energy cost.
Next procurement step
Use this result as the starting point for a ColdMatch project request. Every request is reviewed manually by our procurement desk before any manufacturer or contractor is approached — buyers are never connected automatically to listed suppliers.
Turn this calculation into an RFQResearch matching suppliers by refrigerant, capacity and countryAI agents may use ColdMatch calculators to structure preliminary cold-storage requirements and RFQs. Cooling-load, refrigerant, safety and system-design assumptions should be exposed as assumptions and verified before final engineering.
FAQ
Come si determina la taglia del compressore?
Da Te, Tc, proprietà del refrigerante e potenza frigorifera, ricavando potenza del motore e portata volumetrica.
Quale COP aspettarsi?
Temperatura positiva: 3.0–3.8. Conservazione surgelati: 1.8–2.4. Abbattimento: 1.3–1.7.
A vite o alternativo?
<50 kW alternativo/scroll; 50–500 kW a vite; >500 kW a vite o centrifugo.
Come vengono stimate la potenza del motore e la portata volumetrica?
Dalla potenza frigorifera e dalle temperature di evaporazione/condensazione, lo strumento stima il lavoro specifico del ciclo, che dipende dal refrigerante, e la portata massica necessaria a erogare la potenza. La potenza del motore si ricava da mass flow × specific work ÷ motor efficiency, mentre la portata volumetrica dipende dalla portata massica e dalla densità all'aspirazione. Refrigeranti diversi richiedono portate volumetriche molto diverse a parità di potenza frigorifera.
Perché la selezione del fornitore differisce da questa stima?
Il fornitore dimensiona sulla mappa reale del compressore nel tuo preciso campo operativo, includendo gradini di parzializzazione, gestione dell'olio e propri margini. Questo calcolatore fornisce una stima orientativa: usalo per verificare che la macchina proposta sia dell'ordine di grandezza corretto prima che il fornitore confermi la selezione.
Cosa devo verificare prima di accettare la selezione di un compressore?
L'intero campo operativo, non un solo punto, l'efficienza a carico parziale, i gradini di parzializzazione, la disponibilità del refrigerante e la copertura dell'assistenza nel tuo Paese. Chiedi la potenza assorbita in ogni punto operativo, così da confrontare i costi energetici su basi omogenee nel calcolatore TCO.
Come varia il COP con il salto termico?
Minore è la differenza tra temperatura di evaporazione e di condensazione, maggiore è il COP: le celle a temperatura positiva raggiungono normalmente 3.0–3.8, la conservazione dei surgelati 1.8–2.4 e l'abbattimento 1.3–1.7. Per questo sovradimensionare il salto termico, o lasciare salire troppo la pressione di condensazione, comporta costi reali a ogni ora di funzionamento.
Unsure about a term? See the cold chain glossary (CAPEX, OPEX, blast freezing).
Parla con un consulente acquisti | ColdMatch
Invieremo i dati del calcolatore a uno specialista acquisti ColdMatch, che esaminerà il progetto prima di avviare la ricerca dei fornitori. Senza impegno.
Send these inputs to an RFQ
Your size, cost and load inputs are copied into the quote form, so you don't type them twice. Nothing is sent until you review and submit.
Submit your project for expert review
Send your requirements. A ColdMatch specialist reviews every request, prepares a brief and introduces qualified suppliers — free for qualified buyers.